Specification of PANDUIT Cable Lug Medium Voltage
Panduit Cable Lug are suitable for high Electrical spesification. We Have Panduit LCC2/0-12 Code Conductor Lug, Two Hole, Long Barrel, 2/0 AWG Copper Conductor Size, Black Color Code, 1/2" Stud Hole Size, 1.75" Stud Hole Spacing, 1-9/16 Wire Strip Length, 0.13" Tongue Thickness, 0.85" Tongue Width, 1.50" Neck Length, 4.98" Overall Length.
Copper Compression Connector Installation:
1. Use a connector marked for the wire size and wire material to be used. Never use a copper connector on aluminum wire.
2. Strip wire insulation to approximate length shown on tool chart. Do not nick or ring the conductor strands.
3. Clean the wire.
4. Insert stripped wire into connector until the wire stops.
5. Using installation tooling shown on other side, insert connector in die and crimp between color bands or knurl markings. Required number of compressions shown in.
6. After crimping, inspect for sharp edges, flash or burrs and remove if present.
Heat Shrink Insulation Instruction :
1. Refer to catalog for tubing size
2. Cut tubing to length allowing insulation coverage as desired. Allow a minimum of 1 1/2-inch overlap on wire insulation.
3. Shrink with a standard propane torch or heat gun, Moving from crimped portion of connector toward insulated wire. Adhesive flow at ends indicates shrinkage complete.