Specification of N2XSY Medium High Voltage Cable
Technical Data
Conductor: Cu Round Conductor, Multi Wire Stranded Compacted (Rm), Class 2 Acc. To Hrn Hd 383 / Iec 60228 / Din Vde 0295
Inner Screen: Extruded Semi-Conductive Skin On Conductor
Insulation: XLPE (Cross-Linked Polyethylene, Recent Mark: Pe-X) Compound Dix 8 Acc. To Hrn Hd 620 S1
External Screen: Extruded Semi-Conductive Skin On Insulation, Longitudinally Spliced With Insulation (+ Tape Of Conductive Material)
Concentric Conductor: In Inner Layer Corrugated Spirally Wrapped Copper Wires, In External Layer Copper Tape Wrapped In Counter-Helix
Separating Tape
Sheath: PVC Compound DMC-6 ACC. To HRN HD 620 S1
Sheath Colour: Red
Temperature Range:
During Installation:
-5 °C Up To +70 °C
Max. Operating Temp.: +90 °C
At Short Circuit Of Max. 5 S: Up To 250 °C